8 loop addressable panel. Up to 1000 fire zones. 2 x 5 amp power supply and charger. Complies to EN54 parts 2 & 4. Sophisticated cause & effect programming. Supports Apollo (Discovery, Xplorer S90 & Xp95) Hochiki ESP, Nittan Evolution and AV protocols. Internal loop card. Installer friendly 'Auto-learn' and 'Loop Detection' facility. Robust, removable equipment chassis with plug-in connectors. Trouble-free commissioning and fault finding. Dual, flash-based, microprocessor with on-board real time clock. Dedicated RS232 serial port for PC or modem connection. Installer friendly, auto-learn, facility forum. Advanced graphics display and flash memory. Multiple language settings with various character sets. Logo and company can be applied to the LCD display. Technical Specification:. Display - backlit 240 x 64 graphical LCD. LED indicators - 3 red (2 x fire, 1 x alarm), 1 green (power) & 12 amber (fault & system). Loop current - 500mA. Sounder circuits - 8 x 1 amp programmable. Relays -4 x 1 Amp 30v AC/DC Programmable. Auxiliary support - 2 x 24v 500mA. Open collector /logic outputs - 16 programmable (via 2-way relay card). Programmable switch inputs - 16 volt free digital inputs . On board power supply - 2 x 5 amp high efficiency switched mode. Mains supply - 230 V Ac (+10%, -15% tolerance) 50 /60 Hz 1.9 amp. Battery capacity -2 sets of 24v 4 Ah internal minimum. 24v 38 Ah maximum. Charger current - 2 x 2.4 amp DDP monitored. Event log - 1000 fire & event + diagnostic. Cable entry - 20mm Knock-outs. 36 x top, 9 x top rear and 2 x bottom. Dimensions (H x W x D) - 950 x 450 x 188mm. Weight - 23kg. Manufacturer's part number - AP-1003